Plug and play walk in chiller freezer is perfect combination of eficient, reliability, easy installation and simple maintenance condensing unit.

wek-hd

This unit consist of compressor, condenser, and evaporator that assembled in one compact unit for medium and low temperature application.

Start with capacity from 0.5 HP to 2 HP using refrigerant R134a for chiller application and R404a for freezer application. Suitable for people who love simple units and has limited spaces.

Description Model Compressor Type HP Cooling Capacity
(W)1
 Power consumption
(W)1
 Cell volume
bis (m3)2
Nominal current
(A)
Sound pressure level
(dBA/1m)3
 Weight
(kg)
Dimension Design
Chiller

for cold rooms -5°C bis/to +12°C

Refrigerant: R134a

 WEKN 0900 CAJ4461Y 1/2 860 610 11 3.3 57 50  I
 WEKN 1200 CAJ4492Y 3/4 1180 885 18 4.8 59 55  I
 WEKN 1500 CAJ4511Y 1 1440 985 23 5.3 61 56  I
 WEKN 2000 FH4518Y 1 1/2 2000 1300 36 7.1 62 77  II
Freezer

for freezer rooms  -5°C bis/to -25°C

Refrigerant: R404A

 WEKT 1001 CAJ2446Z 1 1000 1080 15 5.9 65 72  II
 WEKT 1201 CAJ2464Z 1 1/2 1400 1390 26 7.6 65 80  II
 WEKT 1501 FH2480Z 2 1800 1930 36 10.5 66 95  II
  1. Performance data at ambient temperatures of +32°C and cooler air intake temperature of +5°C to –18°C. The equipment capacities were measured in accordance with DIN 8942.
  2. The cold store size calculation was made on the basis of the following marginal conditions:
    For cold rooms:
    Ambient temperature of cold store: 32°C
    Insulation thickness: 70 mm (k = 0,27 W/m2K)
    Compressor run time: 16 h
    Charge: 30 kg/m3d
    Goods cooling: 15 K
    For freezer rooms:
    Ambient temperature of cold store: 32°C
    Insulation thickness: 100 mm (k = 0,19 W/m2K)
    Compressor run time: 18 h
    Charge: 30 kg/m2d
    Goods cooling: 4 K
  3. The sound information is provided as specified in DIN 45635. Because cold rooms only have a very low absorption behaviour, we recommend that calculations are based on only a low reduction in sound levels at other distances.